Electrical Communication is a free textbook on the basics of communication technology. See the editorial for more information....


Loading Phantom Group Circuits

loading coil, non-phantomed circuits
Figure 16. Loading coil used on non-phantomed circuits.

Although loading was developed about 1900 and soon was applied to the side circuits, it was not until about 1910 that phantom circuits were successfully loaded.10,11 One reason for this delay was the difficulty of providing the close balance required in the coil windings to prevent excessive crosstalk. A complete loading system for a phantom group is shown in Fig. 18. The theory is illustrated by the simplified circuit of Fig. 19, where the broken arrows represent instantaneous currents and corresponding fluxes produced by the phantom circuit, and the continuous arrows the currents and resulting fluxes produced by the currents in the side circuits.

equivalent cores for loading coils
Figure 17. Equivalent cores for loading coils. Iron dust core (left); Permalloy dust core (center); molybdenum Permalloy dust core (right). (Courtesy Bell Telephone System.)

TABLE I CONSTANTS OF EXCHAXGE PAPER-INSULATED CABLES, COPPER CONDUCTORS

Gauge

Resistance R, Ohms per Loop mile 68° F

Capacitance C, Microfarads per Mile

Leakance G, Micromhos per Mile 1000 Cycles

Characteristic Impedance Magnitude, Ohms 1000 Cycles

26 (BST)

440

0.079

2.1

942 /-44.5°

24 (DSM)

274

0.084

2.2

721 /-44.20

22

171

0.082

2.1

576/-440

19

85

0.084

2.2

402/-430

19 (Special)

85

0.066

1.7

453 / -43°

NOTE: Inductance is 0.001 henry per loop mile for all gauges.

The currents in the side circuits produce adding fluxes, and the maximum inductance is therefore obtained for loading the side circuits. In the phantom loading coil, however, these currents are in opposite directions through identical windings, and thus neither side circuit will produce magnetic flux in the core of the phantom loading coil. Similarly, the phantom-circuit currents pass through the separate side-circuit coils in the same direction, and since these windings are identical, no magnetic flux is produced in the side-circuit coils by the phantom-circuit current. Under these conditions of balance there is no crosstalk due to magnetic coupling.

loading phantom and side cable circuits
Figure 18. Standard method of loading phantom and side cable circuits in the Bell System.

TABLE II CHARACTERISTICS OF EXCHANGE CABLE CIRCUITS

Circuit

Constants at 100

0 Cycles - 68° F

Nominal

Cable(1)

Loading(2)

Characteristic Impedance(3)

Propagation Constant per Mile Xepers Radians

Attenuation, Decibels per Mile

Cutoff Cycles per Second

26-BST

NL

942 /-44.5°

0.3278 + j0. 3322

2.86

H-88

1192/-20.8°

.2076 + j0.5403

1.80

24-DSM

XL

721 /-44. 2°

.2664 + j0.2715

2.31

H-88

1074/-14.60

.1414 + j0.5341

1.23

B-88

14167- 8.1°

.1078 + j0.7298

0.94

....

22-CSA

XL

576/-43.80

.2065 + j0.2134

1.79

M-88

905/-13.70

.1060 + j0.4341

0.92

2860

H-88

1051/- 9.7°

.0907 + j0.5185

0.79

3510

H-135

1306/- 6.3°

. 0729 + j0. 6402

0.63

2820

B-88

1420/- 5.3°

.0689 + j0.718

0.60

4960

B-135

17657- 3.3°

.0549 + j0.890

0.48

3990

19-CXB

XL

4027-42.8°

.1446 + j0.1551

1.26

M-88

8617- 9.4°

.0568 + j0.4302

0.49

2830

H-88

10177- 5.2°

.0487 + j0.5194

0.42

3460

H-135

12837- 3.3°

.0388 + j0.6455

0.34

2790

B-88

1395/- 2.8°

.0386 + j0.725

0.34

4900

B-135

1742 /- 1.7°

.0304 + j0.900

0.26

3950

19-DXB

XL

453/-42.80

. 1282 + j0.1375

1.11

M-88

9567- 7.4°

.0505 + j0.3796

0.44

3190

H-88

1137/- 5.2°

.0432 + j0.4590

0.38

3910

H-135

1425/- 3.3°

.0345 + j0.5694

0.30

3150

B-88

15657- 2.8°

.0342 + j0.641

0.30

5520

B-135

1952/- 1.8°

.0270 + j0.795

0.24

4450

(1) Paper-insulated cables. See Table I for primary constants.

(2) Numerals indicate total inductance of loading coils in millihenrys, letters indicate load coil spacing as follows: NL, non-loaded; M, 9000 feet; H, 6000 feet; B, 3000 feet.

(3) Midsection iterative impedance in cases of loaded circuits. Magnitude in ohms.

Although M-88 and H-135 loading is in service, it is no longer used in new installations.

What is called flutter may occur in loaded circuits simultaneously providing telephone and telegraph facilities.21 The relatively low-frequency telegraph currents passing through the windings cause corresponding changes in the effective resistance and the inductance of the coils. These produce variations in the transmitting efficiency of the coils, and thus the talking currents vary and produce a "fluttering" effect.

current and flux due to phantom and side circuits
Figure 19. Broken arrows represent current and flux due to phantom. Full arrows represent currents and flux due to side circuits.



Last Update: 2011-05-30